My company had quite a few MGE UPS and we wanted to download and install some managment software in the server incase of power trip, so as to shut down the servers gracefully incase the power fail to come back. We are still using MGE pulsar extreme 2200. So can I use the PowerChute Business Edition to manage it?
www.mgeups.com
Pulsar Evolution
2200/3000/3000 XL
Installation and user
manual
Summary of the content on the page No. 2
MGE UPS Systems 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636 For service call 1-800-438-7373 www.mgeups.com IMPORTANT SAFETY INSTRUCTIONS Read before installing product SAVE THESE INSTRUCTIONS. This manual contains important instructions for 89347, 89348, and 89349 that should be followed during installation and maintenance of the UPS and batteries. Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The Pulsar Evolution range has been designed wit
Summary of the content on the page No. 3
Introduction CAUTION: Safety of persons w The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source. w Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel. w The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the protected equipment does not exceed 3.5 mA by checki
Summary of the content on the page No. 4
Foreword Using this document Information may be found in two ways, using: w the contents; w the index. Pictograms IMPORTANT: Important instructions that must always be followed. NOTE: Information, advice, help. WARNING: Indicates present eminent danger, precautionary action required. CAUTION: Indicates to proceed with caution, precautionary action required. Visual indication. Action. Audio indication. In the illustrations on the following pages, the symbols below are used: LED off. LED on. LED
Summary of the content on the page No. 5
Contents 1. Presentation 1.1 Overall view .................................................................................................................................. 7 Tower position ..................................................................................................................................7 Rack position....................................................................................................................................7 1.2 Back ......................
Summary of the content on the page No. 6
Contents 6. Appendices 6.1 Technical data ..............................................................................................................................24 Simplified diagram..........................................................................................................................24 Technical characteristics ................................................................................................................25 Examples of battery backup times ............
Summary of the content on the page No. 7
1. Presentation 1.1 Overall view Tower position Dimensions in inches (W x H x D) Evolution 2200 Evolution 3000 17.24 (19') x 3.56 (2U) x 25.2 Evolution 3000 XL Weight in lbs Evolution 2200 75 Evolution 3000 82 Evolution 3000 XL 46 Rack position D H W 3400723100/AD - Page 7 P U L S A R Evolution 3 0 0 0 P U L S A R Evolution 3 0 0 0
Summary of the content on the page No. 8
P 0 3 - 5 1. Presentation 1.2 Back Pulsar Evolution 2200 USB communications port. 1 Data line protection R IN 34Z5 U.P.S. 1 RS232 RS232 communications port. 2 OUT SITE WIRING AC Input FAULT WARNING AC Input Volt 120V~1O 3 battery cabinets max Amps 16A MAX 2 Hertz 50/60 Hz BATTERY CONNECTOR TO BATTERY 72Vdc, 7Ah AC Output Volt 120V~1O 344-50282-00 Volt: 72Vdc 40A Hertz 50/60 Hz CABINET W/VA 1540W/1920VA Connector for automatic detection of an Pb 3 U.S. PAT. N
Summary of the content on the page No. 9
1. Presentation 1.3 Control panel 15 Illuminated ON/OFF button for the receptacles. Operation on battery power. 16 17 UPS fault. Battery fault. Overload. 18 Group 1 programmable receptacles supplied with power. 19 1 2 Group 2 programmable receptacles supplied with power. 20 Booster or fader mode. 21 Bar graph indicating percent load at output. 22 % % 23 Bar graph indicating the battery charge level. 76 to 100%. 51 to 75%. 26 to 50%. 0 to 25%. 3400723100/AD - Page 9
Summary of the content on the page No. 10
2. Installation 2.1 Unpacking and parts check 26 25 27 28 29 30 31 32 26 RS232 communications cable for Windows Operating Systems. For UNIX/Linux Operating Systems, please order, for free, the following part number: 66090 USB communications cable. 27 28 Telescopic rails for mounting in 19' bay with mounting hardware. 29 Two securing systems for equipment power cords. 30 CD-ROM with the Solution-Pac and UPS Driver software. 31 Product documentation. 32 Two supports for the upright position. Pa
Summary of the content on the page No. 11
2. Installation 2.2 Upright installation (tower position) Connect the two supports for the upright position. 3400723100/AD - Page 11 P U L S A R Evolution 3 0 0 0 P U L S A R Evolution 3 0 0 0
Summary of the content on the page No. 12
Summary of the content on the page No. 13
R 34Z5 U.P.S. AC Input AC Input Volt 120V~1O Amps 16A MAX Hertz 50/60 Hz BATTERY CONNECTOR AC Output Volt 120V~1O Volt: 72Vdc 40A Hertz 50/60 Hz W/VA 1540W/1920VA U.S. PAT. No. 6,094,363 AC Output 2. Installation 2.4 Connecting the protected equipment CAUTION: Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS. 1 - Re
Summary of the content on the page No. 14
Data line protection Data line protection IN IN RS232 RS232 OUT OUT SITE WIRING WARNING SITE WIRING WARNING 3 battery cabinets FAULT 3 battery cabinets FAULT max for 3000 max for 3000 12 battery cabinets 12 battery cabinets max for 3000XL max for 3000XL 72Vdc, 9Ah 72Vdc, 9Ah BATTERY CONNECTOR TO BATTERY Only for 3000 TO BATTERY Only for 3000 344-50297-00 Volt: 72Vdc 40A CABINET 344-50297-00 Pb CABINET Pb U.S. PAT. No. 6,094,363 2. Installation 2.5 Connection to the RS232 or USB communi
Summary of the content on the page No. 15
Data line protection IN RS232 OUT SITE WIRING WARNING 3 battery cabinets FAULT max for 3000 12 battery cabinets max for 3000XL 72Vdc, 9Ah TO BATTERY Only for 3000 344-50297-00 CABINET Pb 2. Installation 2.7 Installation of the communications-card option 1 - Remove the slot cover 5 secured by two screws. 2 - Insert the card in the slot. 5 3 - Secure the cover with the two screws. Slot for the communications-card It is not necessary to shut down the UPS to option. install the communications c
Summary of the content on the page No. 16
Summary of the content on the page No. 17
3. Operation 3.3 Operation on battery power (following failure of AC-input power) Transfer to battery power The AC-input power is out of tolerances, LED 16 goes ON. During operation on battery power, the buzzer beeps every ten seconds. The equipment connected to the UPS is supplied by the battery. 16 1 2 % % Threshold for the low-battery warning When the threshold is reached, the buzzer beeps every three seconds. The low-battery warning threshold can be set by the user, with the “UPS Driver”
Summary of the content on the page No. 18
Summary of the content on the page No. 19
3. Operation Voltage-thresholds tab Configurable function Default setting Options Output voltage on battery power 120 V 100 V - 127 V Upper threshold for transfer to battery power 151 V 141 V to 153 V Fader-mode cut-in threshold 132 V 127 V to 138 V Booster-mode cut-in threshold 102 V 92 V to 108 V Lower threshold for transfer to battery power 89 V 80 V to 94 V Maximum input-voltage range Disabled Enabled (1) Lower threshold for transfer to battery mode = 70 V Sensitivity tab Configurable functi
Summary of the content on the page No. 20
Pulsar Evolution UPS
500
800
1100
1500
2200
Power VA/W
500/350
800/560
1100/700
1440/1000
1920/1540
Versions
1U Rack
Mini-Tower and 1U Rack
Versatile Tower/2U Rack
Installation possibilities
Rackable, stackable,
Mini-Tower version: vertical or horizontal
Rackable, stackable or
vertical tower
Rack version: rackable or stackable
vertical tower w support base
or wall-mount
Number of outlets
4
4
4
4
6
Including Powershare outlets
2
2
2
2
2
Battery extension (EXB modules)
–
–
–
–
From 1 to 3 EXBs
Performance
Technology
High-Frequency Line-Interactive
Automatic voltage regulation
Booster/Fader
Output voltage waveform
Sinewave
Input voltage tolerances
92V/138V, adjustable to 80V/153V via supplied UPS-Driver software
Frequency
50/60 Hz, auto-select
Output voltage on battery power
120VAC (adjustable to 100/120/127V via supplied UPS-Driver software)
Input Connection
NEMA 5-15 straight plug, 6 foot cord
NEMA 5-20P
Output Connection
NEMA 5-15
Features
Automatic battery test
Weekly (interval adjustable via supplied UPS-Driver software)
Hot swappable batteries
x
x
x
x
x
Cold start
x
x
x
x
x
Deep discharge protection
x
x
x
x
x
UPS-Driver for Windows
Settings: Input voltage tolerances, Sensitivity, Battery test, ON/OFF conditions
Data line protection
Surge protection for RJ45 network connection
Network Administration/Monitoring
Communications
1 USB port + 1 Serial port
Software supplied (Solution-Pac CD)
Including local power management software and SNMP proxy-agents for Windows 2000/NT/98
Linux, Netware, OpenServer, Unixware, SUN Solaris, IBM AIX, HP UX, Compaq Tru64, etc.
Communication Expansion Slot
1 slot for optional Network Management Card (66246) or status indication card
Standards/Warranty
Safety
EN 50091-1-1/EN60950(RD),IEC 60950,TÜV GS-Mark
Electromagnetic compatibility
EN 50091-2,EN 50022/B,IEC 62040-2,IEC 61000-3-2,IEC 61000-3-3
Mge Pulsar Evolution 2200 Software Download Windows 10
Design, production and services
ISO 9001
Marking
UL, cUL, FCC Class A, UL1778
Warranty (U.S. and Canada)
2 years, parts and labor
Effective: February 2005
©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.
Mge Pulsar Evolution 2200 Software Download Windows 7
Distributed by:
Power Sources Unlimited (website www.psui.com)
Telephone: (800)966-7784
Fax Number: (508)384-1896
Dimensions, weight and ref.
500
800
1100
1500
2200
Tower dimensions (HxWxD in inches)
–
5.9 x 9.3 x 16.3
5.9 x 9.3 x 19.0
–
Rack dimensions (HxWxD in inches)
1.73 (1U) x 17.2 x 13.9
–
1.73 (1U) x 17.2 x 19.6 1.73 (1U) x 17.2 x 20.6
3.5 (2U) x 17.2 x 25.2
Tower/Rack weights (in =lbs.)
– / 19.8
23.1/–
25.3/35.2
33/41.9
74.7
EXB module weight
–
–
–
–
92.3
Accessories supplied
removable and repositionable 19” rack-mount brackets, universal telescopic rails,
with Rack versions:
mounting hardware kit, rear attachment, cable lock system
Tower ref.
–
89341
89343
89345
–
Rack ref.
89340
–
89344
89346
–
Tower convertible to Rack ref.
–
–
–
–
89347
EXB module ref.
89350
MGE
UPS SYSTEMS
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Characteristics
Battery charge level
Group of 6 outlets for
equipment connection with
2 programmable outlets
Power consumption
Complete user interface:
- on AC input / on battery
- booster/fader mode
- programmable outlet status
- battery replacement required
or UPS fault
Connection
of additional
battery modules
Slot for optional
communications
card
Data line
protection
Automatic recognition
of battery extensions
RS232 communications
port
USB communications
port
Repositionable
logo and battery
access plate
Pulsar
Evolution
2200